UVERS W Unit Heaters-Coolers

  1. Homepage
  2. Products
  3. Unit heaters
  4. UVERS W Unit Heaters-Coolers

UVERS W unit heaters are designed to be fed with hot water from traditional high and low temperature heat sources such as heat pumps or condensing furnaces and can also be fed with chilled water to provide cooling.
The unit heaters are designed for heating and cooling areas such as factory floors, workshops, warehouses, showrooms, sports, and entertainment halls, etc.

PRODUCT DESCRIPTION

UVERS W unit heaters are available in two sizes.
The unit heater consists of:

  • axial fan with AC or EC single phase motor;
  • high-efficiency 2 or 3-row fin coil (the unit heaters with cooling function are only available with 3-row coils);
  • casing made of coated steel sheet;
  • air outlet grille with adjustable blades allowing to set the direction of discharge air.

Accessories:

  • specially designed wall mounting bracket that allows the position of the unit heater to be adjusted at an angle of ± 45° in the horizontal plane and at an angle of 25° in the vertical plane;
  • drip tray for collecting the condensate generated during the cooling process.

OPERATING CONDITIONS

UVERS W units can be fed with water at a maximum temperature of up to 150°C and an operating pressure of up to 1.5MPa.

 

OPERATION MODES

UVERS W unit heaters are designed to be fed with hot water from high and low temperature heat sources such as heat pumps or condensing boilers. They can also be fed with chilled water to provide cooling.

  • 2 sizes,
  • axial fan with AC or EC single-phase motor,
  • high-efficiency 2 or 3-row fin coil,
  • casing made of coated steel sheet,
  • air outlet grille with adjustable blades allowing to adjust the direction of discharge air,
  • coil fed with water at a maximum temperature of up to 150°C and an operating pressure of up to 1.5MPa

Technical data

  • Dimensions

    Dimensions

    A[mm]

    B[mm]

    h[mm] L[mm] d1 d2

    556

    527

    460 445 3/4′ 3/4′

     

    AC fan parameters

    Supply voltage [V]

    230

    Motor power [W]

    140

    Current [A]

    0,65

    Speed [min-1]

    1420

    IP

    54

    Operating temperature

    60oC

     

    Heating capacity

    Number of coil rows

    II

    Air flow [m3/h]

    2050

    Heating capacity [kW], air outlet temperature [oC] and resistance of water flow [kPa]

    Water temp. [°C]

    Air inlet temperature [ºC]

    kW

    °C

    kPa

    90/70

    5

    25,1 39  10,4

    10

     23,6 42 8,8

    16

     20,6 45 7,1
     20 19,0 47  6,0

    80/60

    5

     21,2  34 7,5

    10

     19,2  37  6,1

    16

     16,9  40 4,7
    20  15,3 42  3,9

    70/50

    5

     17,7 29  5,1

    10

    15,5  31 4,1

    16

    13,3  35 2,9
     20  11,8 37  2,3

    60/40

    5

    13,7  24 3,1

    10

     11,9 27  2,3

    16

     9,8 30  1,6
     20  8,3 32  1,2

    50/30

    5

     10,2  19 1,7

    10

     8,4  22 1,2

    16

     6,3  25

     0,7

     20 4,9  27  0,4

    40/30

    5

    9,6 18  6,2

    10

     7,8 21 4,1

    16

     5,6 24 2,1
     20  4,1 26  1,2

     

    Noise level [dB(A)]

    Noise level — sound pressure level taking into account the sound absorption in the room A=100m2 and directivity factor Q=2 at a distance of 5 m

    53

    Unit weight

    Weight [kg]

    26
  • Dimensions

    Dimensions

    A[mm]

    B[mm]

    h[mm] L[mm] d1 d2

    556

    527

    460 445 3/4′ 3/4′

     

    AC fan parameters

    Supply voltage [V]

    230

    Motor power [W]

    140

    Current [A]

    0,65

    Speed [min-1]

    1420

    IP

    54

    Operating temperature

    60oC

     

    Heating capacity

    Number of coil rows

    III

    Air flow [m3/h]

    1900

    Heating capacity [kW], air outlet temperature [oC] and resistance of water flow [kPa]

    Water temp. [°C]

    Air inlet temperature [ºC]

    kW

    °C

    kPa

    90/70

    5

    31,3 51 8,7

    10

    30,2 52 8,2

    16

    25,8 56 5,9
     20 23,8 57 5,6

    80/60

    5

    26,7 44 6,3

    10

    25,4 46 5,7

    16

    21,3 49 4,1
    20 19,4 50 3,4

    70/50

    5

    22,1 38 4,3

    10

    20,6 39 3,8

    16

    16,9 42 2,5
     20 15,2 43 2,1

    60/40

    5

    17,6 31 2,8

    10

    16,0 32 2,3

    16

    12,5 35 1,4
     20 10,7 37 1,2

    50/30

    5

    13,1 24 1,5

    10

    11,4 26 1,2

    16

    8,2 29 0,7
     20 6,4 30 0,4

    40/30

    5

    12,2 23 5,3

    10

    10,3 24 3,8

    16

    7,2 27 1,8
     20 5,4 28 1,0

     

    Cooling capacity

    Number of coil rows

    III

    Air flow [m3/h]

    1900

    1700*

    Cooling capacity [kW] , air outlet temperature [oC], water flow [m3/h] and resistance of water flow [kPa]

    Water temp. [°C]

    Air inlet temperature [ºC]

    kW

    ºC

    m3/h

    kPa

    kW

    ºC m3/h kPa

    7/12

    28

    8,2 19 1,4 25,6 7,8 18 1,3 23,3

    25

    6,1 17 1,0  15,3  5,7 17 1,0 13,4

    22

    4,7  15 0,8  9,7  4,4  14 0,8 8,5

    12/16

    28

    5,7 20 1,2 19,5  5,3  20 1,1  17,2

    25

     4,3  19 0,9 12 4,0  18 0,9 10,6

    22

    2,9  18 0,6 5,9 2,7  17 0,6  5,2

    Cooling capacities are given at 50% relative humidity.

    *Recommended airflow when the unit is used for cooling.

    Noise level [dB(A)]

    Noise level — sound pressure level taking into account the sound absorption in the room A=100m2 and directivity factor Q=2 at a distance of 5 m

    53

    Unit weight

    Weight [kg]

    28
  • Dimensions

    Dimensions

    A[mm]

    B[mm]

    h[mm] L[mm] d1 d2

    556

    527

    460 350 3/4′ 3/4′

     

    EC fan parameters

    Supply voltage [V]

    230

    Motor power [W]

    140

    Current [A]

    1,45

    Speed [min-1]

    1660

    IP

    54

    Operating temperature

    40oC

     

    Heating capacity

    Number of coil rows.

    II

    Air flow [m3/h]

    2350

    Heating capacity [kW], air outlet temperature [oC] and resistance of water flow [kPa]

    Water temp. [°C]

    Air inlet temperature [ºC]

    kW

    °C

    kPa

    90/70

    5

    27,2 37 12,2

    10

    24,9 40 10,3

    16

    22,3 43 8,3
     20 21,3 45 7,5

    80/60

    5

    23,0 32 8,8

    10

    20,8 35 7,2

    16

    18,3 39 5,5
    20 17,2 41 4,9

    70/50

    5

    18,9 28 5,9

    10

    16,8 30 4,7

    16

    14,3 34 3,4
     20 13,5 36 2,9

    60/40

    5

    14,8 23 3,7

    10

    12,8 26 2,8

    16

    10,5 29 1,8
     20 9,2 31 1,4

    50/30

    5

    11,0 18 2,0

    10

    9,0 21 1,4

    16

    6,7 24 0,8
     20 5,3 26 0,5

    40/30

    5

    10,4 17 7,2

    10

    8,4 20 4,7

    16

    6,0 23 2,4
     20 4,6 25 1,4

     

    Noise level [dB(A)]

    Noise level — sound pressure level taking into account the sound absorption in the room A=100m2 and directivity factor Q=2 at a distance of 5 m

    56

    Unit weight

    Weight [kg]

    24
  • Dimensions

    Dimensions

    A[mm]

    B[mm]

    h[mm] L[mm] d1 d2

    556

    527

    460 350 3/4′ 3/4′

     

    EC fan parameters

    Supply voltage [V]

    230

    Motor power [W]

    140

    Current [A]

    1,45

    Speed [min-1]

    1660

    IP

    54

    Operating temperature

    40oC

     

    Heating capacity

    Number of coil rows

    III

    Air flow [m3/h]

    2150

    Heating capacity [kW], air outlet temperature [oC] and resistance of water flow [kPa]

    Water temp. [°C]

    Air inlet temperature [ºC]

    kW

    °C

    kPa

    90/70

    5

    33,9 49 10,2

    10

    31,1 51 8,6

    16

    27,9 54 6,9
     20 25,8 55 5,9

    80/60

    5

    28,8 43 7,4

    10

    26,2 45 6,1

    16

    23,0 47 4,7
    20 20,9 49 3,9

    70/50

    5

    23,8 36 5,1

    10

    21,3 38 4,1

    16

    18,2 41 3,0
     20 16,2 42 2,4

    60/40

    5

    19,0 30 3,2

    10

    16,5 32 2,4

    16

    13,5 34 1,6
     20 11,5 36 1,2

    50/30

    5

    14,2 23 1,8

    10

    11,7 26 1,2

    16

    8,8 28 0,8
     20 7,0 30 0,5

    40/30

    5

    13,2 22 6,2

    10

    10,6 24 4,0

    16

    7,7 26 2,1
     20 5,8 28 1,2

     

    Cooling capacity

    Number of coil rows

    III

    Air flow [m3/h]

    2150

    1700*

    Cooling capacity [kW] , air outlet temperature [oC], water flow [m3/h] and resistance of water flow [kPa]

    Water temp. [°C]

    Air inlet temperature [ºC]

    kW

    OC

    [m3/h]

    kPa

    kW

    OC [m3/h] kPa

    7/12

    28

     8,7  19 1,5  28,4 7,8  18 1,3  23,3

    25

    6,6 17 1,1 17,6  5,7  17 1,0 13,4

    22

    5,1 15 0,9 11,1  4,4 15 0,8  8,5

    12/16

    28

    6,2 20 1,3  22,5  5,3 20 1,1 17,2

    25

    4,7  19 1,0  13,8 4,0 18 0,9  10,6

    22

    3,1 18 0,7 6,8 2,7  17 0,6 5,2

    Cooling capacities are given at 50% relative humidity.

    *Recommended airflow when the unit is used for cooling.

    Noise level [dB(A)]

    Noise level — sound pressure level taking into account the sound absorption in the room A=100m2 and directivity factor Q=2 at a distance of 5 m

    56

    Unit weight

    Weight [kg]

    26
  • Dimensions

    Dimensions

    A[mm]

    B[mm]

    h[mm] L[mm] d1 d2

    677

    686 620 461 3/4′ 3/4′

     

    AC fan parameters

    Supply voltage [V]

    230

    Motor power [W]

    250

    Current [A]

    1,15

    Speed [min-1]

    1350

    IP

    54

    Operating temperature

    60oC

     

    Heating capacity

    Number of coil rows

    II

    Air flow [m3/h]

    4500

    Heating capacity [kW], air outlet temperature [oC] and resistance of water flow [kPa]

    Water temp. [°C]

    Air inlet temperature [ºC]

    kW

    °C

    kPa

    90/70

    5

    52,1 37 17,8

    10

    47,9 40 15,1

    16

    42,8 44 12,1
     20 39,0 46 10,2

    80/60

    5

    44,1 32 12,7

    10

    40,0 35 10,5

    16

    35,1 39 8,1
    20 31,9 41 6,7

    70/50

    5

    36,2 27 8,6

    10

    32,2 31 6,8

    16

    27,5 34 5,0
     20 24,4 36 3,9

    60/40

    5

    28,5 23 5,3

    10

    25,8 26 4,0

    16

    20,1 29 2,7
     20 17,2 31 2,0

    50/30

    5

    21,0 18 2,9

    10

    17,3 21 2,0

    16

    12,9 24 1,2
     20 10,1 26 1,0

    40/30

    5

    20,0 17 10,5

    10

    16,1 20 6,8

    16

    11,5 23 3,5
     20 8,6 25 2,0

     

    Noise level [dB(A)]

    Noise level — sound pressure level taking into account the sound absorption in the room A=100m2 and directivity factor Q=2 at a distance of 5 m

    62

    Unit weight

    Weight [kg]

    41
  • Dimensions

    Dimensions 

    A[mm]

    B[mm]

    h[mm] L[mm] d1 d2

    677

    686 620 461 1′ 1′

     

    AC fan parameters

    Supply voltage [V]

    230

    Motor power [W]

    250

    Current [A]

    1,15

    Speed [min-1]

    1350

    IP

    54

    Operating temperature

    60oC

     

    Heating capacity

    Number of coil rows

    III

    Air flow [m3/h]

    4200

    Heating capacity [kW], air outlet temperature [oC] and resistance of water flow [kPa]

    Water temp. [°C]

    Air inlet temperature [ºC]

    kW

    OC

    kPa

    90/70

    5

     65,5 49 16,5

    10

    60,2 51 13,9

    16

    53,9  54 11,2
     20  49,8 55 9,5

    80/60

    5

    55,7 42 11,9

    10

     50,5  45 9,8

    16

    44,4  47 7,6
    20 40,6  49 6,3

    70/50

    5

    46,1  36 8,1

    10

    41,4  38  6,5

    16

    35,2 40 4,7
     20 31,2 42  3,7

    60/40

    5

    36,6  30  5,1

    10

    31,7 32 3,9

    16

    26,0 34 2,6
     20 22,3  36 2,0

    50/30

    5

    27,3  23 2,8

    10

    22,5  25 2,0

    16

    17,1 28

    1,2

     20  13,4 29  1,0

    40/30

    5

     25,4  22 10,0

    10

    21,1 24  6,5

    16

     14,8 26 3,4
     20 11,1 28  2,0

     

    Cooling capacity

    Number of coil rows

    III

    Air flow [m3/h]

    4200

    3200*

    Cooling capacity [kW] , air outlet temperature [oC], water flow [m3/h] and resistance of water flow [kPa]

    Water temp. [°C]

    Air inlet temperature [ºC]

    kW

    OC

    [m3/h]

    kPa

    kW

    OC [m3/h] kPa

    7/12

    28

    15,1 20 2,6 17,2 13,3 19 2,3 13,8

    25

    12,0 18 2,1 11,5 10,1 17 1,7 8,5

    22

    9,1  15 1,6 7,1 7,7 15 1,3 5,2

    12/16

    28

    11,3 21 2,4 14,9  9,5 20 2,0 11,0

    25

    8,5  19 1,8 9,0 7,1 19 1,5 6,6

    22

    5,5 18 1,2 4,2 4,6 18 1,0 3,1

    Cooling capacities are given at 50% relative humidity.

    *Recommended airflow when the unit is used for cooling.

    Noise level [dB(A)]

    Noise level — sound pressure level taking into account the sound absorption in the room A=100m2 and directivity factor Q=2 at a distance of 5 m

    62

    Unit weight

    Weight [kg]

    47
  • Dimensions

    Dimensions

    A[mm]

    B[mm]

    h[mm] L[mm] d1 d2

    677

    686 620 423 3/4′ 3/4′

     

    EC fan parameters

    Supply voltage [V]

    230

    Motor power [W]

    332

    Current [A]

    2,16

    Speed [min-1]

    1300

    IP

    54

    Operating temperature

    70oC

     

    Heating capacity

    Number of coil rows

    II

    Air flow [m3/h]

    5800

    Heating capacity [kW], air outlet temperature [oC] and resistance of water flow [kPa]

    Water temp. [°C]

    Air inlet temperature [ºC]

    kW

    OC

    kPa

    90/70

    5

    60,2 35 23,8

    10

    55,2 37 20,2

    16

    49,4  41 16,2
     20 45,5  45  13,6

    80/60

    5

     50,8  30 16,9

    10

     46,2 33  13,9

    16

    40,4  36 10,7
    20 36,7  39 8,8

    70/50

    5

    41,6 25 11,4

    10

    38,4  28 9,0

    16

    31,6 32 6,5
     20 28,5 34 5,2

    60/40

    5

    32,7 21 7,0

    10

     28,2 24 4,6

    16

    23,1  27  3,5
     20 19,6  30 2,5

    50/30

    5

    24,1 17 3,8

    10

    19,8 19 2,6

    16

     14,8 23

    1,4

     20 11,5 26 1,0

    40/30

    5

     23,0  16 14,0

    10

     18,5 19 9,0

    16

    13,2  22 4,6
     20 9,8 25 2,5

     

    Noise level [dB(A)]

    Noise level — sound pressure level taking into account the sound absorption in the room A=100m2 and directivity factor Q=2 at a distance of 5 m

    64

    Unit weight

    Weight [kg]

    46
  • Dimensions

    Dimensions

    A[mm]

    B[mm]

    h[mm] L[mm] d1 d2

    677

    686 620 423 1′ 1′

     

    EC fan parameters

    Supply voltage [V]

    230

    Motor power [W]

    332

    Current [A]

    2,16

    Speed [min-1]

    1300

    IP

    54

    Operating temperature

    70oC

     

    Heating capacity

    Number of coil rows

    III

    Air flow [m3/h]

    5450

    Heating capacity [kW], air outlet temperature [oC] and resistance of water flow [kPa]

    Water temp. [°C]

    Air inlet temperature [ºC]

    kW

    OC

    kPa

    90/70

    5

    77,2 45  22,9

    10

    70,9 47 19,3

    16

    63,5  50 15,5
     20  58,4  52 13,2

    80/60

    5

    65,5 39 16,5

    10

     59,4 41 13,5

    16

     52,2  44 10,5
    20  47,5  46 8,6

    70/50

    5

    54,1 33 11,2

    10

    48,2 35 8,9

    16

    41,2 38  6,5
     20  36,4  40  5,2

    60/40

    5

    42,8  27 7,1

    10

     37,1  29 5,3

    16

    30,3 32 3,6
     20  25,9 34 2,6

    50/30

    5

     31,8 21 3,9

    10

     26,2  24 2,7

    16

     19,8 26

    1,5

     20 15,7 29 1,0

    40/30

    5

     29,9  20 13,7

    10

     24,1 23  8,9

    16

    17,3 25 4,6
     20  13,0 27 2,6

     

    Cooling capacity

    Number of coil rows

    III

    Air flow [m3/h]

    5450

    3200*

    Cooling capacity [kW] , air outlet temperature [oC], water flow [m3/h] and resistance of water flow [kPa]

    Water temp. [°C]

    Air inlet temperature [ºC]

    kW

    OC

    [m3/h]

    kPa

    kW

    OC [m3/h] kPa

    7/12

    28

    17,3 21 3,0 21,9 13,3  19 2,3 13,8

    25

    14,0 18 2,4 15,1 10,1 17 1,7 8,5

    22

     10,6  16 1,8 9,3 7,7 15 1,3 5,2

    12/16

    28

    13,2 21 2,8 19,6 9,5 20 2,0 11,0

    25

    9,9  20 2,1 11,7 7,1  19 1,5 6,6

    22

    6,4 19 1,4 5,5 4,6 18 1,0 3,1

    Cooling capacities are given at 50% relative humidity.

    *Recommended airflow when the unit is used for cooling.

    Noise level [dB(A)]

    Noise level — sound pressure level taking into account the sound absorption in the room A=100m2 and directivity factor Q=2 at a distance of 5 m

    64

    Unit weight

    Weight [kg]

    52