TERM-E Electric Unit Heaters

  1. Homepage
  2. Products
  3. Unit heaters
  4. TERM-E Electric Unit Heaters

The TERM-E heating units with axial fans, metal casing and electric heaters are designed to heat rooms such as: industrial halls, workshops, warehouses, commercial pavilions, sports and entertainment halls etc.
The heating and ventilation units are made through adding roof or wall intakes and intake boxes for establishing a mixing proportion of fresh and circulating air to TERM-E heating units.
The units are adapted to work in a horizontal position as ceiling units and in a vertical position as wall units.

PRODUCT DESCRIPTION

The unit includes:

  • axial fan;
  • electric heaters with spirally rolled aluminium finned tubes;
  • external casing made of lacquered steel sheet;
  • protection net made of galvanized steel sheet against accidental contact with heaters,
  • options: single-row grid, slot ventilator or outlet nozzle.

The casing variant with the following items is recommended to use with the units which are planned to be operated as ceilings ones:

  • slot diffuser – for heating a zone of human presence by a secondary air stream;
  • discharge cone – for increasing a range of supply air stream.
  • At the client’s request the units can be manufactured with casing and heaters made of stainless steel.

 

Additional automation elements (option):

  • power and control box (AT) equipped with overcurrent circuit breakers, relays and  contactors, signalling lamps, switches: AUTO | STOP, 3-step power regulation and air flow capacity and HEATING | VENTILATION.
  • temperature regulator (RTA) for automatic change of heat output depending on the temperature in the room
  • time programmer (ZG) for control of unit’s operation in weekly mode.

Technical data

  • Dimensions

    Fan parameters
    Voltage [V] 230
    Motor power [kW] 0,14
    Current [A] 0,63
    Revolutions [rpm] 1400
    IP 54
    Insulation class F
    Operating temperature do +60oC
    Thermal powers of devices with electric heaters
    Air capacity [m3/h] 2100
    Thermal power ranges [kW] 6 / 12 /18
    Operation noise level [dB(A)]
    At the distance of 1m 61
    At the distance of 5m 57
    Unit weight
    Weight [kg] 30
  • Dimensions

    Fan parameters
    Voltage [V] 230
    Motor power [kW] 0,18
    Current [A] 0,77
    Revolutions [rpm] 1400
    IP 54
    Insulation class F
    Operating temperature do +60oC
    Thermal powers of devices with electric heaters
    Air capacity [m3/h] 2900
    Thermal power ranges [kW] 9 / 18 / 27
    Operation noise level [dB(A)]
    At the distance of 1m 63
    At the distance of 5m 59
    Unit weight
    Weight [kg] 34