OPTIMAX-RGS Compact Air Handling Units

  1. Homepage
  2. Products
  3. Air handling units
  4. OPTIMAX-RGS Compact Air Handling Units

OPTIMAX-RGS is a range of energy-efficient compact air handling units that incorporate the latest thermal and ventilation technology.
The high-efficiency counter flow heat exchanger enables the recovery of thermal energy from exhaust air with up to 90% efficiency. Additionally, the high-efficiency fans with EC motors are used to minimize electricity consumption. The double-skin panels are 50mm thick and insulated with mineral wool to reduce heat loss to the environment. They also provide excellent acoustic insulation for the working fans.
The units are fitted with vertical air outlets so that they can be installed in confined spaces such as niches.

OPTIMAX-RGS

  • sizes and airflow ranges
  • heat recovery efficiency up to 90%
  • EC motors
  • PLUG & PLAY controls
  • certificates
  • available versions
  • 3D BIM models
  • RGS-05      250 ÷ 700 m3/h
    RGS-10      600 ÷ 1,800 m3/h
    RGS-25      1,100 ÷ 2,700 m3/h
    RGS-40      2,300 ÷ 4,700 m3/h
    RGS-60      3,900 ÷ 6,300 m3/h
    RGS-90      5,500 ÷ 9,500 m3/h

Functions of OPTIMAX-RGS air handling unit:

  • Air filtration

    • panel filters
  • Heating

    • water heating coil
    • electric heater
  • Heat recovery

    • counter flow heat exchanger
  • Air transfer

    • direct-driven fans with EC motors

Applications

The OPTIMAX-RGS compact air handling units are mainly used in:

  • industrial facilities
  • shopping centres
  • warehouses
  • hospitals
  • cinemas
  • educational facilities
  • swimming pools

More information on the product

Controls for OPTIMAX-CROSS units

The use of Plug&Play control systems for air handling units provides comfort at the lowest possible running costs, as well as safety and monitoring of the operation of control devices against damage.

The purpose of such systems is to limit the human impact as much as possible to the direct operation of these systems, so that the operator role is only limited to setting the required parameters. The rest is provided by the automatic control system, which adapts to both indoor conditions and changing outdoor conditions.

Control components (sensors, pressure switches, …) and actuators (valves, actuators, …) cooperate with a freely programmable controller (equipped as standard with an open Modbus RTU communication protocol (RS-485) or optional: LON Works, BACnet IP, Ethernet, Modbus TCP / IP), which is configured based on the requirements of the client (project).

Read More

Product Selection Programs

PSP provide the correct selection of air handling units, display all necessary parameters, and allow you to print out a report summarising the selection. This solution offers customers a professional and comprehensive service that saves time. The programmes allow for the selection of nearly all of our products.

Go to PSP

Technical data

  • Dimensions

    Dimensions 
    B
    [mm]
    HB
    [mm]
    LB
    [mm]
    BW
    [mm]
    HW
    [mm]
    LW
    [mm]
    HP
    [mm]
    H
    [mm]
    Masa
    [kg]
    600 900 1350 200 500 150 100 1210 180

    The standard version of the AHU can be modified in terms of the materials used after consultation with our technical department.
    The modifications’ scope must be approved during the quotation preparation stage.

     

     

     

     

  • Dimensions

    Dimensions 
    B
    [mm]
    HB
    [mm]
    LB
    [mm]
    BW
    [mm]
    HW
    [mm]
    LW
    [mm]
    HP
    [mm]
    H
    [mm]
    Masa
    [kg]
    800 1100 1750 300 700 150 100 1410 291

    The standard version of the AHU can be modified in terms of the materials used after consultation with our technical department.
    The modifications’ scope must be approved during the quotation preparation stage.

  • Dimensions

    Dimensions 
    B
    [mm]
    HB
    [mm]
    LB
    [mm]
    BW
    [mm]
    HW
    [mm]
    LW
    [mm]
    HP
    [mm]
    H
    [mm]
    Masa
    [kg]
    1000 1200 1950 350 900 150 100 1510 380

    The standard version of the AHU can be modified in terms of the materials used after consultation with our technical department.
    The modifications’ scope must be approved during the quotation preparation stage.

  • Dimensions

    Dimensions 
    B
    [mm]
    HB
    [mm]
    LB
    [mm]
    BW
    [mm]
    HW
    [mm]
    LW
    [mm]
    HP
    [mm]
    H
    [mm]
    Masa
    [kg]
    1200 1400 2150 400 1100 150 100 1710 514

    The standard version of the AHU can be modified in terms of the materials used after consultation with our technical department.
    The modifications’ scope must be approved during the quotation preparation stage.

  • Dimensions

    Dimensions 
    B
    [mm]
    HB
    [mm]
    LB
    [mm]
    BW
    [mm]
    HW
    [mm]
    LW
    [mm]
    HP
    [mm]
    H
    [mm]
    Masa
    [kg]
    1400 1500 2350 450 1300 150 120 1830 696

    The standard version of the AHU can be modified in terms of the materials used after consultation with our technical department.
    The modifications’ scope must be approved during the quotation preparation stage.

  • Dimensions

    Dimensions 
    B
    [mm]
    HB
    [mm]
    LB
    [mm]
    BW
    [mm]
    HW
    [mm]
    LW
    [mm]
    HP
    [mm]
    H
    [mm]
    Masa
    [kg]
    1700 1900 2950 500 1600 200 120 2230 1100

    The standard version of the AHU can be modified in terms of the materials used after consultation with our technical department.
    The modifications’ scope must be approved during the quotation preparation stage.

We value your privacy